House Circuit Breaker Wiring Diagrams

–Check local regulations for restrictions and permit requirements before beginning electrical work– The user of this information is responsible for following all applicable regulations and best practices when performing electrical work. If the user is unable to perform electrical work themselves, a qualified electrician should be consulted.

This page contains wiring diagrams for a service panel breaker box and circuit breakers including: 15amp, 20amp, 30amp and 50amp, as well as a GFCI breaker and an isolated ground circuit.

Circuit Breaker Panel Box Wiring Diagram

wiring diagram for a house circuit breaker service panel box

This diagram illustrates some of the most common circuits found in a typical 200 amp circuit breaker service panel box. The breakers are installed in a panel so that contact is made with one of two hot bus bars running down the middle of the box. The hot wire for a branch circuit is connected to the breaker by a set screw on the base. The neutral and ground wires for the circuit are connected to a bar along the side of the service panel box. The neutral and grounding bars in the panel may be separate or, in the case of older service panels, the same bar may be used for both purposes.

Wiring for a 15 Amp, 120 Volt Circuit Breaker

wiring diagram for a 15 amp, 120 volt circuit breaker

This wiring diagram illustrates installing a 15 amp circuit breaker for a 120 volt branch circuit. The 14/2 awg cable for this circuit includes 2 conductors and 1 ground wire. A 15 amp circuit is usually used for wall receptacle outlets and room light fixtures.

Wiring for a 20 Amp, 120 Volt Circuit Breaker

wiring diagram for a 20 amp 120 volt circuit breaker

This diagram illustrates the arrangement for a 20 amp, 120 volt double receptacle circuit with a shared neutral wire. This arrangement is typically used in a kitchen where two separate appliance circuits are needed in close proximity to each other.

Wiring for a 20 Amp, 240 Volt Appliance Circuit Breaker

wiring diagram for a 20 amp, 240 volt circuit breaker

This circuit breaker wiring diagram illustrates installing a 20 amp circuit breaker for a 240 volt circuit. The 12/2 gauge cable for this circuit includes 2 conductors and 1 ground. The white wire is used for hot in this circuit and it is marked with black tape to identify it as hot. A neutral wire is not used in this circuit. A dedicated 20 amp circuit like this is used for heavy household appliances like large portable window air conditioners.

Wiring for a 30 Amp, 240 Volt Circuit Breaker

wiring diagram for a 30 amp, 240 volt circuit breaker

This circuit breaker wiring diagram illustrates installing a 30 amp circuit breaker for a 240 volt circuit. The 10/3 cable for this circuit has 3 conductors and no ground. A 30 amp circuit like this is usually found in household water heater circuits and older installations for clothes dryers and kitchen cooking ranges. For a new installation of a kitchen range, use the diagram below for a 50amp circuit.

Wiring for a 50 Amp, 240 Volt Circuit Breaker

wiring diagram for a 50 amp, 240 volt circuit breaker

This wiring diagram illustrates installing a 50 amp circuit breaker for a 240 volt circuit. The 6 gauge cable for this circuit has 3 conductors and 1 ground. A 50 amp circuit like this is used for newer clothes dryers and kitchen range installations.

Wiring a GFCI Circuit Breaker

wiring diagram for a gfci circuit breaker

This diagram illustrates wiring for a circuit breaker with a built-in ground fault circuit interrupter or gfci. This 20 amp, 120 volt breaker is a form of gfci that can be installed at the circuit source. This kind of circuit is used for dishwashers, whirlpool spas and other locations where water contact is likely.

Wiring for a 15 Amp Isolated Ground Circuit

wiring diagram for a 15 amp, 120 volt isolated ground circuit

An isolated-ground receptacle makes use of an extra wire to provide a separate, dedicated ground in the circuit. In a 15 amp circuit, the red wire in a 14/3 cable is used for this purpose and marked green at both ends. It is connected to the grounding terminal on the receptacle. The other cable wires are connected as with any other branch circuit except for the ground wire. The bare copper ground wire is NOT connected to the receptacle, instead it is connected to the grounding terminal inside the metal electrical box where the receptacle is housed.

A special isolated-ground receptacle is require for this circuit and can be identified by the orange color and a small triangle imprinted on the face. When connecting the wires, the isolated ground wire (the red wire pictured here) is marked with green tape or paint on each end and connected to the grounding bar in the service panel and to the grounding terminal on the receptacle.

This arrangement is used for computers and sensitive A/V equipment such as a home theater to eliminate noise interference in the audio and video output that can be caused by the random electrical activity on the grounding wires throughout a dwelling's electrical system. These are also required in hospitals where sensitive medical monitors may be affected by grounding noise in the wiring which can cause disruption in their critical functions.

–In these wiring diagrams, the brass colored terminals represent the hot side of the device and the silver colored terminals represent the neutral side. Ground wires and terminals are in green, including a green dot representing the builtin grounding terminal found in most metal outlet boxes.

–By code, the number of conductors allowed in a box are limited depending on box size. Conductors include wires, devices like switches and receptacles, and some other metal parts. Check here to calculate the number of conductors allowed in a box before adding new wiring, etc.